Polar Cloud
- Action Buttons
- Adding Alerts
- Adding Users
- Adding Users to Alerts
- Alert Action Triggers
- Alert Types
- Calculated Fields
- Can I change my login details ?
- Configure a 4–20mA sensor reading
- Configure a pulse water meter
- Create a conditional alert with several thresholds
- Device Dashboard
- Download Polar App on your phone
- Editing Users
- First Time Setup
- Groups
- Home Screen Navigation
- How do I get my login details?
- How to edit a users account details
- Poll Rates
- Read connection status and Site licence usage
- Remote Programming
- Removing A User
- Schedulers
- Sites
- Software License
- User Roles
- Viewing Active Alerts
- Viewing Historical Alerts
- What happens during an internet or power outage?
- What happens to schedules and alerts during an outage?
- Show all articles (16) Collapse Articles
Create a conditional alert with several thresholds
Use a Condition alert when the same measurement must notify at several thresholds within one alert. Each threshold belongs to this alert.
- Open the device dashboard, choose Alerts, then Add Alert.
- Set Alert Type to Condition, name it and add a useful description.
- In Settings, choose the measurement tag.
- Select a Condition Type, enter its comparison value and choose Add.
- Use Add Another Condition for the remaining thresholds. The displayed controls allow conditions to be reordered and edited.
- Set the required Trigger/Resolve actions, if commissioned, and Advanced options including Enabled, Notifications Enabled and Check Every.
- Choose Create, then confirm that the alert appears in the configured list.
The comparison options shown are is Null, is not Null, Greater than, Greater than or Equal to, Less than, Less than or Equal, Equal to and not Equal to.
Example: falling and recovering tank level
The example uses three less-than conditions: 80, 60 and 40. With a correctly configured percentage-level tag, the intended behaviour is a new notification as the level falls through each threshold, followed by restoration notifications as it rises past 40%, 60% and 80%.
The demonstration uses an analogue-input tag labelled in mA while describing a percentage-level example. Before applying these values to a real tank, configure and verify a percentage-level tag. Do not enter percentage thresholds against an unconverted current reading.
These thresholds are examples, not recommended operating levels for every installation. Test falling and rising readings against the intended sequence. The recording does not establish how simultaneous threshold crossings, exact equality, skipped samples or condition ordering affect message delivery.
Match the check interval to the tag
If the tag polls every 15 minutes, the alert cannot offer a check interval shorter than 15 minutes. First change the tag to five-minute polling on the Live page if five-minute alert checking is required, then set Check Every in the alert. This is not a guaranteed five-minute notification-delivery time.