Polar Cloud
- Action Buttons
- Adding Alerts
- Adding Users
- Adding Users to Alerts
- Alert Action Triggers
- Alert Types
- Calculated Fields
- Can I change my login details ?
- Configure a 4–20mA sensor reading
- Configure a pulse water meter
- Create a conditional alert with several thresholds
- Device Dashboard
- Download Polar App on your phone
- Editing Users
- First Time Setup
- Groups
- Home Screen Navigation
- How do I get my login details?
- How to edit a users account details
- Poll Rates
- Read connection status and Site licence usage
- Remote Programming
- Removing A User
- Schedulers
- Sites
- Software License
- User Roles
- Viewing Active Alerts
- Viewing Historical Alerts
- What happens during an internet or power outage?
- What happens to schedules and alerts during an outage?
- Show all articles (16) Collapse Articles
Configure a pulse water meter
Identify the connected pulse input, the physical meter’s starting total, the units used by that total, and the meter’s exact pulse specification. Record whether that specification is litres per pulse or pulses per litre.
- Open the relevant device dashboard and enable edit mode.
- Open the pulse tile’s three-dot menu and choose Settings.
- Set Name, Tile Group and the matching display unit.
- In Formatting, set Multiplier, Calibration Offset and Precision.
- In Polling, select the required interval.
- In Advanced, tick Is Cumulative. Keep Has Analogue unticked; the interface states that analogue and cumulative processing are mutually exclusive.
- Save the tile, then save the overall configuration. If a device restart is required, allow it to finish, refresh and verify communication.
Worked configuration example
An example uses a Calibration Offset of 125000 as the starting reading, with the Multiplier to 0.5 and Precision to 1. With the factor and units below, each pulse represents 0.5 litres. This calculated example must be verified against the installed meter.
Set the multiplier in litres per pulse
For a volume display in litres, Multiplier is litres per pulse. A multiplier of 0.5 means 0.5 litres per pulse. A meter producing one pulse per 100 litres uses multiplier 100.
| Meter specification | Multiplier for litres |
|---|---|
| 0.5 litres per pulse | 0.5 |
| 1 litre per pulse | 1 |
| 100 litres per pulse | 100 |
Check the direction of the manufacturer’s specification. A specification in pulses per litre must first be converted to litres per pulse. Use matching units for the multiplier, displayed total and calibration offset.
Align the starting total without resetting
You can align the displayed total without resetting the module. Subtract the module’s current represented volume from the physical meter total, using the same units.
Calibration Offset = physical meter total in litres − (raw pulse count × litres per pulse)
If the portal value is already scaled to volume, do not multiply it again. Exclude any existing offset from the represented volume used in this calculation. Record the physical total and module count together so pulses arriving between observations do not distort the baseline.
Calculated example: A physical total of 125000 litres and a module count of 1000 pulses at 0.5 litres per pulse represent 500 litres. The required offset is 124500 litres. Verify the actual installation after saving.
Before considering Reset All Counters
Reset All Counters resets both pulse counters at the same time. It is not an individual-channel reset. The MB4442 revision 4 manual also lists uptime/downtime counters as affected. Do not reset the module just to align one meter without considering every affected counter.
A qualified installer must first record both pulse counts, the corresponding physical meter totals, existing scaling/offsets and any runtime baselines in use. Confirm the effect on dependent totals, alerts and reporting with Polar support before any reset. This guide does not establish how reset or rollover affects every history/report view.
If a reset is deliberately approved for the whole module, use the procedure for the exact hardware and firmware in its applicable manual, then re-establish and verify every affected baseline. With a verified zero pulse count, the relevant meter’s offset equals its physical total in the chosen units. This article provides no command-level reset instructions.
Prove the reading
Verification checks: record the physical meter total and portal total together; produce a known measured volume or known number of pulses; compare the increase in both totals; verify a later timestamped history entry. At 0.5 litres per pulse, ten pulses should add five litres. At 100 litres per pulse, ten pulses should add 1000 litres.
Is Cumulative enables interval-based processing for a cumulative measurement. Ask Polar support about the report presentation and reset or rollover handling for your integration.
Record the final factor, units, starting total, offset, polling interval and verification results in the commissioning record.