Skip to main content
Print

Create a conditional alert with several thresholds

Create a conditional alert with several thresholds

Use a Condition alert when the same measurement must notify at several thresholds within one alert. Each threshold belongs to this alert.

  1. Open the device dashboard, choose Alerts, then Add Alert.
  2. Set Alert Type to Condition, name it and add a useful description.
  3. In Settings, choose the measurement tag.
  4. Select a Condition Type, enter its comparison value and choose Add.
  5. Use Add Another Condition for the remaining thresholds. The displayed controls allow conditions to be reordered and edited.
  6. Set the required Trigger/Resolve actions, if commissioned, and Advanced options including Enabled, Notifications Enabled and Check Every.
  7. Choose Create, then confirm that the alert appears in the configured list.

The comparison options shown are is Null, is not Null, Greater than, Greater than or Equal to, Less than, Less than or Equal, Equal to and not Equal to.

Example: falling and recovering tank level

The example uses three less-than conditions: 80, 60 and 40. With a correctly configured percentage-level tag, the intended behaviour is a new notification as the level falls through each threshold, followed by restoration notifications as it rises past 40%, 60% and 80%.

The demonstration uses an analogue-input tag labelled in mA while describing a percentage-level example. Before applying these values to a real tank, configure and verify a percentage-level tag. Do not enter percentage thresholds against an unconverted current reading.

Condition alert with three thresholds. Use a correctly scaled percentage tag for the illustrative level example; the demonstration tag label is mA.
Condition alert with three thresholds. Use a correctly scaled percentage tag for the illustrative level example; the demonstration tag label is mA.

These thresholds are examples, not recommended operating levels for every installation. Test falling and rising readings against the intended sequence. The recording does not establish how simultaneous threshold crossings, exact equality, skipped samples or condition ordering affect message delivery.

Match the check interval to the tag

If the tag polls every 15 minutes, the alert cannot offer a check interval shorter than 15 minutes. First change the tag to five-minute polling on the Live page if five-minute alert checking is required, then set Check Every in the alert. This is not a guaranteed five-minute notification-delivery time.

Table of Contents