Polar Cloud
- Action Buttons
- Adding Alerts
- Adding Users
- Adding Users to Alerts
- Alert Action Triggers
- Alert Types
- Calculated Fields
- Can I change my login details ?
- Configure a 4–20mA sensor reading
- Configure a pulse water meter
- Create a conditional alert with several thresholds
- Device Dashboard
- Download Polar App on your phone
- Editing Users
- First Time Setup
- Groups
- Home Screen Navigation
- How do I get my login details?
- How to edit a users account details
- Poll Rates
- Read connection status and Site licence usage
- Remote Programming
- Removing A User
- Schedulers
- Sites
- Software License
- User Roles
- Viewing Active Alerts
- Viewing Historical Alerts
- What happens during an internet or power outage?
- What happens to schedules and alerts during an outage?
- Show all articles (16) Collapse Articles
Configure a 4–20mA sensor reading
Before starting, identify the physical input used, the sensor’s signal range, its engineering range and the required display unit. Use an account with Technician access. The example uses a 0–16 bar pressure transducer; a tank-level application must use its own sensor range and units.
Open the input settings
- Open the relevant device and its dashboard.
- Enable edit mode in the Live Data area.
- Find the analogue input matching the wired channel. Open its three-dot menu and choose Settings.
- In Edit Data Tile, set Name and Tile Group.
- Expand Display and select the appropriate Measurement and source unit. The pressure example uses Environmental › Pressure › Bar (bar), rather than milliamps. Choose the icon as needed.
Set the signal and sensor ranges
Expand Advanced and tick Has Analogue. The demonstrated configuration uses:
| Field | Video example | Meaning |
|---|---|---|
| Type | Raw | The option shown for this example. |
| Signal Min | 4000 | 4mA expressed in microamps. |
| Signal Max | 20000 | 20mA expressed in microamps. |
| Output Minimum (Units) | 0 | Sensor engineering value at 4mA. |
| Output Maximum (Units) | 16 | Sensor engineering value at 20mA, in bar for this example. |
Use the actual sensor specification for the output range. For a sensor specified as 4–20mA = 0–10m, the corresponding illustrative output range is 0 to 10, with a matching length unit. This tank example is a range-mapping example; the video does not demonstrate tank geometry, sensor mounting offsets or volume calculations.
Formatting and polling
Expand Formatting. The fields are Multiplier, Calibration Offset and Precision. Precision controls decimal places. The screen describes Calibration Offset as being added to the final value.
For a reading already scaled to the desired engineering units, a multiplier of 1 and offset of 0 are the neutral settings. A pressure-to-head conversion depends on the application and its required display unit. Use a suitable conversion for the actual sensor and fluid.
Expand Polling and choose the required reading interval. The previously confirmed platform minimum is five minutes. Polling affects collection frequency; it does not correct a scaling error.
Save and verify
- Click Save in Edit Data Tile.
- Save the overall device/dashboard configuration using its save control.
- If the configuration requires a device restart, allow it to finish, then refresh and check communication.
- Ensure the intended tag is enabled and its unit is correct.
- Compare the displayed reading with a known reference and verify fresh timestamped history.
Calculated verification example: with multiplier 1 and offset 0, a linear 0–16 bar mapping should give 0 bar at 4mA, 8 bar at 12mA and 16 bar at 20mA. Test using appropriate qualified procedures and record actual results. These calculated examples do not prove the installed sensor’s accuracy.