Invertek Optidrive P2 Variable Speed Drives

This guide will show you how to connect the Polar Monitoring Gateway to the Invertek Optidrive P2 Variable Speed Drive. It will also take you through the setup and parameters required on the Optidrive P2 to ensure communications to the Polar Gateway.

Steps to follow:

  1. Connect power to the Gateway.
  2. Connect RS-485.
  3. Final checks.
  4. Power on the system.
  5. Configure the Invertek Optidrive P2 Serial Parameters
 

Invertek Optidrive P2 Connection Setup

Invertek Optidrive Wiring Diagram
Wiring Diagram
1. Connect power to the Gateway.
Power Polar Gateway

Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.

2. Connect RS-485.
Polar Gateway RS-485

Wire the RS-485 cable to allow communication with the Polar Gateway. Connect A+ => Pin 8 and the B- => Pin 7.

3. Final checks
Before you switch on the Gateway and the device make sure you have done everything correctly in the previous steps.
 
  • Make sure the wiring is secure – no short circuits.
  • Check if the power cables are not loosely wired to the Gateway.
  • Check if the power cables are not loosely wired to the device.
  • Re-check the RS-485 twisted pair cable is correctly wired.
4. Power on the system

Now you are ready to go, you can now switch on the Polar Gateway and the Invertek Optidrive P2.  

5. Configure Invertek Optidrive P2 Serial Parameters
In order for the Gateway to correctly communicate with the Invertek Optidrive P2 controller, there will need to be some changes made to the communication parameters. 

Note: It is critical to change the default settings to reflect the table below.

Serial Communication Setup

NameDescriptionParameterDefaultRequired
Command Source ModeCommunication ProtocolP1-1204
Digital Inputs Function SelectFunction of digital input for control modeP1-1311
Extended Menu AccessParameter Access ControlP1-140201
Communication AddressDevice ID/Unit ID/Node IDP5-0111
Serial SpeedModbus RTU Communication SpeedP5-03115.29.6
ParityError-checking process and stop bitP5-04n-1n-1

You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.