fbpx
How can we help?
< All Topics
Print

Delta CP2000 Irrigation and Solar Variable Speed Drives

This guide will show you how to connect the Polar Gateway to Delta CP2000 Variable Speed Drive. It will also take you through how to setup the parameters required on device to ensure communications to the Gateway.

Steps to follow:

  1. Connect power to the Gateway.
  2. Connect RS-485.
  3. Final checks.
  4. Power on the system.
  5. Configure the Delta DP2000 Serial Parameters
 

Delta CP2000 Connection Setup

Delta CP2000 Wiring Diagram
Wiring Diagram
1. Connect power to the Gateway.
Power Polar Gateway

Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.

2. Connect RS-485.
Delta CP2000 RS-485 To Polar Gateway

Wire the RS-485 cable to allow communication with the Polar Gateway device. Connect A+ =>  SG+ B => SG-.

3. Final checks
Before you switch on the device make sure you have done everything correctly in the previous steps.
 
  • Make sure the power is OFF while doing the cable wiring.
  • Re-check if there are no short circuits.
  • Check if the power cables are not loosely wired to the Gateway.
  • Check if the power cables are not loosely wired to the Variable Speed Drive.
  • Re-check the RS-485 twisted pair cables is correctly connected A+ =>  SG+ B => SG-.
4. Power on the system

Now you are ready to go, you can now switch on the Polar Gateway and the Delta CP2000. 

5. Configure Delta CP2000 Serial Parameters
In order for the Gateway to correctly communicate with the Delta CP2000 controller, there will need to be some changes made to the communication parameters. 

Note: It is critical to change the default settings to reflect the table below.

Serial Communication Setup

NameDescriptionParameterDefaultRequired
Communication AddressSlave address09-0011
Communication SpeedBaud Rate09-019.69.6
Communication ProtocolProtocol09-041=7,N,2(ASCII)12=8,N,1 (RTU)

You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.

Previous Connecting the Polar Gateway to Lovato DCRL8
Next Delta DT3 Series Temperature Controller
Table of Contents
Copyright © 2022 Polar Monitoring